Product Overview
Environmental Space | Indoor/Outdoor – Euroclass Dca |
---|---|
Suitable Applications | For outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser) and/or horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV and/or broadcast. Easy to install in ducts, tunnels and/or tubes. |
Construction
FIBER CABLE CONSTRUCTION
FIBER TYPE | FIBER COUNT | SUBUNIT COLOR | SUBUNIT COLOR 2 |
---|---|---|---|
OM4 | 12 | TIA coding (Gxxxxxx.T): Natural | Europe coding (Gxxxxxx.0): Natural |
Fiber Color Coding | TIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown, Gray, White, Red, Black, Yellow, Violet, Pink, Aqua |
---|---|
Fiber Color Coding 2 | Europe coding (Gxxxxxx.0): Red, Natural, Yellow, Blue, Green, Violet, Brown, Black, Orange, Aqua, Pink, White |
Cable Core Water Tight | Yes |
---|---|
Cable Core Water Blocking | Waterblocking Glass Yarns |
Bulk Cable Weight | 37 kg/km |
SubUnit Specifications
Number of Active Subunits | 1 |
---|---|
Number of Subunit Positions | 1 |
Fibers Per Subunit | 12 |
Jacket Specifications
Number of Jackets | Single Jacket |
---|---|
Type of Armor | Non-Armored |
Outer Jacket
OUTER JACKET MATERIAL
MATERIAL | NOMINAL DIAMETER | NOMINAL WALL THICKNESS | RIPCORD |
---|---|---|---|
LSZH – Low Smoke Zero Halogen (Flame Retardant) | 5.8 mm | 0.8 mm | 0 |
Table Notes | Standard color: Orange. Available colors: Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Black, Lime Green |
---|
Optical Characteristics
Fiber Core Diameter | 50 µm |
---|---|
Max Attenuation at 1300 nm | 1.0 dB/km |
Max Attenuation at 850 nm | 2.9 dB/km |
Mechanical Characteristics
MECHANICAL TESTS
DESCRIPTION | TESTED STANDARD | REQUIREMENT/VALUE | ACCORDING TO FAMILY SPECIFICATION |
---|---|---|---|
Cable Min. Bend Radius Installation (Short Term) | IEC 60794-1-21-E6 | 116 mm | IEC 60794-3-10 |
Cable Min. Bend Radius Operation (Long Term) | IEC 60794-1-21-E11 | 58 mm | IEC 60794-3-10 |
Cable Max. Tensile Strength Installation (Short Term) | IEC 60794-1-21-E1 | 1500 N (337 lbf) | IEC 60794-3-10 |
Cable Max. Tensile Strength Operation (Long Term) | IEC 60794-1-21-E1 | 500 N (112 lbf) | IEC 60794-3-10 |
Cable Max. Crush Resistance Installation (Short Term) | IEC 60794-1-21-E3 | 15 kN/m | IEC 60794-3-10 |
Cable Max. Crush Resistance Operation (Long Term) | IEC 60794-1-21-E3 | 7.5 kN/m | IEC 60794-3-10 |
Temperature Range
Operating Temp Range | -30 °C to +70 °C |
---|---|
Installation Temp Range | -5 °C to +50 °C |
Storage Temp Range | -30 °C to +70 °C |
Product Material
UL Rating/Flame Test | Non-UL Rated |
---|
Standards
IEC Flammability | IEC 60332-1-2 |
---|---|
IEC 60754-1 – Halogen Amount | Zero |
IEC 61034-2 – Smoke Density Min. Transmittance | 60% |
CPR Euroclass | Dca-s2,d1,a1 |
REACH | Compliant |
ISO/IEC Compliance | IEC 60794 |
UV/ Sunlight Protection | yes |
History
Update and Revision | Revision Number: 0.131 Revision Date: 07-19-2021 |
---|
Part Numbers
ITEM # | COLOR | PUT-UP TYPE | LENGTH | EAN |
---|---|---|---|---|
GUSNE12.042100 | Black | Reel | 2,100 m | 8719605157560 |
GUSNE12.002100 | Orange | Reel | 2,100 m | 8719605084071 |
GUSNE12.004100 | Orange | Reel | 4,100 m | 8719605084088 |
GUSNE12.026100 | Turquoise | Reel | 6,100 m | 8719605084101 |